The abnormality of the inspection and treatment of the high voltage wireless nuclear phase meter device is as follows:
1. Abnormal phenomenon: The transmitter indicator 1 is on, and there is no signal from the receiving host.
Cause: The instrument hardware is faulty. Nuclear phase meter
Treatment methods: Return to factory maintenance.
2. Abnormal phenomenon of high voltage wireless nuclear phase meter : The transmitter does not beep and the light does not flash.
Reasons: 1) The battery is low and cannot start.
2) Instrument hardware failure. Nuclear phase meter
Treatment: Check after charging for 1 hour. If it still fails to start, it is a hardware failure and needs to be returned to the factory for repair.
3. Abnormal phenomenon of the high-voltage wireless nuclear phase meter : the buzzer sounds, the light flashes, and the receiving host does not display the waveform or frequency. Nuclear phase meter
Reason: 1) The line voltage is lower than the applicable voltage of the instrument.
2) Instrument hardware failure. Nuclear phase meter
Treatment method: Use the applicable voltage marked on the instrument for inspection. If it is still abnormal, return it for repair.
4. Abnormal phenomenon of the high-voltage wireless nuclear phase analyzer : The two transmitters are connected to the same line, the buzzer sounds, the light flashes, and the receiving host displays out of phase.
Reason: 1) The line voltage is much higher than the applicable voltage of the instrument.
2) High-voltage wireless nuclear instrument hardware failure. Nuclear phase meter
Treatment method: Use the applicable voltage marked on the instrument for inspection. If it is still abnormal, return it for repair.
High-voltage wireless nuclear phase meter technical parameters and parts function description
Technical parameters
1. Accuracy: In-phase error ≤ 3 degrees, different phase error ≤ 5 degrees
2. The collectors X, Y and host line of sight transmission distance ≤ 80m
3. Collector voltage: 0.38KV-500KV
4. Host power supply: 9V±2V
5. Collector power supply: 7.5±1.5V
6. Working temperature: -35°C-+60°C
7. Insulated telescopic rod: 650mm in the reduced state and 3300mm in the extended state.
8. Sample status: Line or equipment live parts.
9. Height above ground: less than 20 meters.
Dear Customer:
Thank you for your attention to our products. In addition to this product introduction, the company also has insulation ladders, high-voltage insulation mats, cable fault testers, high-voltage measuring instruments, insulation boots gloves pressure test equipment, power safety equipment cabinets, etc. Introduction, if you are interested in our products, welcome to inquire. Thank you!
Hammer Crusher
Hammer Crusher for Mining Crusher
A hammer crusher is a crusher in which a hammer hits the material that is being crushed. In the hammer crusher, crushing takes place by impact between the hammers and breaker plates. The hammer crusher has pivoted hammers on a horizontal shaft.
TyCrusher parts provide all kinds of crusher, we have sufficient stock. At the same time we can also customize products to meet your various needs. In addition, We stock high-quality aftermarket replacement Wear Parts such as manganese steel wear liners, internal crusher mechanical and wearing components, slurry and dredging pump wear parts, bi-metal wear blocks, rock drilling consumables and mill liners. We cover all areas of the crusher to include products. All Mining Wear Parts products are manufactured and warranted by Mining Wear Parts.