Design and Application of Power Surveillance System of Australia-US Pharmaceutical Suzhou Co., Ltd.

Arkori Qingqing

Jiangsu Ankerui Electric Appliance Manufacturing Co., Ltd., Jiangyin, Jiangsu 214405, China

Abstract: This paper introduces the power monitoring system of Australia-US Pharmaceutical Suzhou Co., Ltd. It adopts smart power meter to collect various electrical parameters and switch signals at the distribution site. The system adopts the on-site local networking method. After networking, it communicates via the field bus and transmits it to the background. The Acrel-2000 power monitoring system realizes the real-time monitoring of power distribution circuit substations in substations.

Keywords: Large-scale manufacturing enterprises; Australia-US pharmaceutical Suzhou Co., Ltd.; 0.4KV substation; smart power meter; Acrel-2000; power monitoring system

0 Overview

AUS Pharmaceutical Suzhou Co., Ltd. is located 400 meters north of the intersection of Zhongtang Road and Zhenbei Road in Huqi District, Suzhou City, Jiangsu Province.

This project is the power monitoring of Suzhou Aumei Substation. According to the requirements of power distribution system management, power monitoring must be performed on the low-voltage distribution outlets within the two substations of the Wuhu standard factory building to ensure the safety, reliability, and efficiency of electricity usage.

Acrel-2000 low-voltage intelligent power distribution system takes full advantage of the latest developments in modern electronic technology, computer technology, network technology and fieldbus technology, and conducts distributed data collection and centralized monitoring and management of the power distribution system. The secondary equipment of the distribution system is networked. Through the computer and the communication network, the field devices of the decentralized power distribution station are connected into an organic whole, and remote monitoring and centralized management of the power grid operation are realized.

1 System Structure Description

The monitoring system mainly realizes the 0.4kV power distribution system of 2 substations of Suzhou Omega Pharmaceutical Co., Ltd. for power monitoring and power management. The monitoring range includes two ACR220ELK self-manufactured ACR220ELK self-manufactured models of two low-voltage line cabinets, connecting cabinets and feeder cabinets of two 0.4KV transformer substations for remote real-time monitoring and power management. The system consists of 45 multi-function power meters, divided into 2 buses. The two buses are pulled to the serial port server through a shielded twisted pair cable and uploaded to the duty room monitoring host through data processing to achieve data connectivity between the meter on the bus and the monitoring host.

The monitoring system adopts a hierarchical distributed structure, ie station control layer, communication layer and bay layer; as shown in Figure (1):

Figure (1) Low-voltage network topology

The main equipment for the bay is: Ankerui multi-function network power meter, switch, analog acquisition module and intelligent circuit breaker. These devices are corresponding to the corresponding primary equipment installed in the electrical cabinet, these devices are used RS485 communication interface, through the on-site MODBUS bus network communication, data acquisition on the spot.

The network communication layer is mainly a protocol conversion isolator. Its main function is to convert RS485 signals into RS232 signals and complete the data exchange between the field layer and the station control layer.

Station control management: equipped with high-performance industrial computers, monitors, UPS power supplies, printers and other equipment. The monitoring system is installed on the computer to collect and display the operating status of the field equipment and display it to the user in the form of human-computer interaction.

The above network instruments all use RS485 interface and MODBUS-RTU communication protocol. RS485 adopts shielded wire transmission. Generally, two wires are used for connection. The connection is simple and convenient. The communication interface is half-duplex communication, that is, both parties can receive and send data. Only data can be sent or received at the same time. The maximum data transmission rate is 10Mbps. The RS485 interface is a combination of balanced drivers and differential receivers. It has enhanced noise immunity and allows up to 32 devices to be connected on the bus. The maximum transmission distance is 1.2 km.

2 main functions of the power monitoring system

2.1 Data Acquisition and Processing

Data acquisition is the basis of power distribution monitoring. Data collection is mainly accomplished by the underlying multi-function network instrumentation to achieve local real-time display of remote data. The signals that need to be collected include: three-phase voltage U, three-phase current I, frequency Hz, power P, power factor COSφ, power Epi, and remote device operating status.

Data processing is mainly to display the electrical parameters collected according to requirements in real time and accurately to the user, to achieve the automation and intelligent requirements of the distribution monitoring, and at the same time storing the collected data into the database for user query.

2.2 Human-computer interaction

The system provides simple, easy to use, and good user interface. Using the Chinese interface, the CAD graphic shows the electrical main wiring diagram of the low voltage distribution system, shows the status of the distribution system equipment and the corresponding real-time operating parameters, the screen timing switching tour; dynamic refresh of the screen real-time; analog display; switch display; continuous Record display and so on.

2.3 Historical events

The historical event viewing interface provides convenient and friendly human-computer interaction for the user to view fault records, signal records, operation records, and over-limit records that have occurred. You can view the platform through historical events. You can easily locate your own according to your requirements and query conditions. The historical events that you want to view provide you with good software support for the operation of the entire system.

2.4 Database Establishment and Query

It mainly completes the remote measurement and remote signal acquisition, and establishes a database to generate reports regularly for users to query and print.

2.5 User Rights Management

For different levels of users, different permission groups are set to prevent the losses caused by human misoperation to production and life, and to realize the safe and reliable operation of the distribution system. You can use user management to perform user login, user logout, password change, and add/delete operations to facilitate the user's modification of accounts and permissions.

2.6 Running load curve

The load trend curve function is mainly responsible for regularly collecting incoming lines and important loop current and power load parameters, and automatically generating running load trend curves to facilitate users to know the operating load status of the equipment in a timely manner. Click on the screen button or menu item corresponding to complete switching of the respective function; real-time view the historical trend line or trend curves; curve can be selected to pan, zoom, and other operations range conversion, to help the user into the line fault trend analysis and recall, Provides intuitive and convenient software support for analyzing the health of the entire system.

2.7 Remote Report Query

The main function of the report management program is to design the report style according to the needs of the user, and the data processed in the system is filtered, combined and statistically generated to generate the report data required by the user. This program can also be based on the needs of users of the report file to save, print or summon save, print mode. At the same time, this program also provides users with management functions for generated report files.

The report has the functions of freely setting the query time to realize daily, monthly, and annual energy statistics, data export, and report printing.

3 Case Studies

The monitoring area of ​​the U.S. and U.S. Pharmaceutical Co., Ltd. power monitoring system is 2 substations. This project aims at the electricity monitoring and power management of the 10/0.4kV distribution system in this substation; the monitoring range is 0.4KV low-voltage circuit in the substation. The low-voltage line cabinets, contact cabinets and feeder cabinets are used for remote real-time monitoring and power management.

The ACR220ELK multi-function instrument is used in the in-out line circuit, which is a network power meter designed for the power monitoring needs of power systems, industrial and mining enterprises, public facilities, and intelligent buildings. It can measure all conventional power parameters such as three-phase voltage, Current, active power, reactive power, power factor, frequency, active power, reactive power and other electrical parameters. And this instrument has 4 photoelectric isolation digital input contacts and 2 relay control output contacts. These contacts can be used with intelligent circuit breakers to achieve remote signaling and remote operation of the circuit breaker. The series of network power meters are mainly used in substation automation, distribution network automation, residential power monitoring, industrial automation, energy management systems and intelligent buildings.

The secondary map of low voltage distribution is shown in figure (2). The main function of the power meter remote monitoring is to monitor the electrical parameters of the operating equipment, including: three-phase voltage, current, power, power factor, electrical energy, frequency and other electrical parameters and distribution loops. Three-phase current; remote signal function to display the operating status of field devices, mainly including: switching of the switch, closing operation status and communication failure alarm; when the circuit breaker is dislocated, an alarm signal will be issued to remind the user to deal with the fault in time.

Figure (2) Secondary diagram of low voltage distribution

The remote signaling and telemetry alarm functions mainly complete the monitoring of the switching operation status and load incoming line of the low-voltage outlet loops, and indicate the specific alarm position and audible alarm to the switch displacement and load over-limit pop-up alarm interfaces, prompting the on-duty personnel to deal with them in time. The load limit can be set freely under the corresponding authority. With history query function. See Figure (3) and Figure (4).

Figure (3) Real-time remote alarm information

Figure (4) Historical telemetry alarm information query

The parameter reading function mainly inquires into the electrical parameters of the low-voltage outlet circuit. Supports electrical parameter query at any time, with functions such as data export and report printing. The report queries the electrical parameters of the low-voltage loops for the two transformer substations of the 2 substations, mainly including: three-phase current, active power, active power, and transformer temperature. The names of the loops in this report are associated with the database to facilitate the user to modify the loop name. See Figure (5).

Figure (5) Parameter meter reading

The electricity consumption report function can select the time period to inquire, supports the accumulated electricity inquiry at any time, and has the functions of data export and report printing. Provide accurate and reliable power report for duty personnel. The names of the loops in this report are associated with the database to facilitate the user to modify the loop name. As shown in the figure below, the precise power consumption of each distribution circuit in a certain period of time, the user can directly print the report, and can be saved to other locations in EXCEL format. See Figure (6).

Figure (6) Energy Report

The schematic diagram of the system communication structure mainly shows the network structure of the system. The system adopts a hierarchical distributed structure and simultaneously monitors the communication status of the equipment at the bay level. Green indicates normal communication and red indicates communication failure. See Figure (7).

Figure (7) System Communication Structure

The load trend curve interface allows you to visually check the load operation of the loop. View real-time and historical trend curves, click the corresponding button or menu item to complete the switching of corresponding functions; help the user to enter the trend analysis and fault recall, with curve printing function. Provides intuitive and convenient software support for analyzing the health of the entire system. See Figure (8).

Graph (8) Trend Graph

4 Conclusion

With the development of society and the wide application of electricity, the power monitoring system has become an inevitable choice for large-scale multi-substation users, such as key construction projects, landmark buildings, and large-scale public facilities throughout the country. The Acrel-2000 power monitoring system introduced in this paper is introduced. In Australia and the United States Pharmaceutical Co., Ltd., the application can realize real-time monitoring and power management of power substation low-voltage distribution circuits, not only can display the power status of the circuit, but also has network communication functions, and can be composed of serial server, computer, etc. The power monitoring system facilitates the remote management of the on-duty personnel of the substation, which is conducive to saving the time of energy meter reading and brings informatization into the distribution monitoring. The system analyzes and processes the collected data, displays the operating status of each distribution circuit in the substation in real time, has a pop-up alarm dialog box and voice prompts for the closing and closing of the load, and generates various energy reports and analysis curves. Graphics, etc., to facilitate remote meter reading and analysis, research. The system is safe, reliable and stable, providing real and reliable basis for users of substations to solve electricity problems and achieving better social benefits. [2]

references:

[1]. Ren Zhicheng, Zhou Zhong. Principles and Application Guides for Digital Meters for Electric Power Measurement [M]. Beijing. China Electric Power Press, 2007. 4

[2].Zhou Zhouzhong, et al. Product Selection and Solution for Smart Grid User-end Power Monitoring and Power Management System[M]. Beijing. Machinery Industry Press. 2011.10

Cheer Apparel

Guangzhou Dandy sportswear mainly specializes in custom cheerleading uniforms which include all star cheerleading uniform, Sublimated Cheer Uniforms and cheer practice wears, cheer hair bows and Cheer Warm up.

All stars cheerleading uniform: it's made from 250gsm/260gsm lycra and some popular mystique fabric and custom mesh fabric. Our prices are based on the custom design and fabric required. It's around $ 50-$70

Cheer Practice Wear: It's made from polyester&spandex. We apply for quadruped needles and six stitches, which is firm enough when being stretched hardly. The prices are based on the quantity. It's around $ 12 per pcs

Cheer Hair bows: As for cheer bows, glitter fabric is the fabric we often use which feel and touch better compared with mystique fabric. We also do sublimated bows which are cost effective.

Cheer warm up: it's made from polyester&spandex. Any colors available for custom tracksuits or jackets

cheer uniforms

practice wear (2)

practice wear

cheer uniforms for competition; uniforms for cheerleading;cheap cheer uniforms;all star cheer uniform;customizable cheer uniforms

Guangzhou Dandy Sporting Goods Ltd , https://www.dandysportswear.com